4.3.4 RSD Command
This command for reading D-Register orderly.
Transmission Format
Byte 1 2 3 1 2 1 4 2 1 1
S
C L
T
Command
element
X
Addr RSD ,
Para.
number
, D-Reg. No. SUM
R F
Response
Byte 1 2 3 1 2 1 4 1 4 1
S
T
Command
element
X
Addr RSD , OK , dddd-1 , dddd-2 ,
1 4 1 4 2 1 1
C L
, dddd-(n-1) , dddd-(n) SUM
R F
- Para. number : 1~32.
- dddd : Indicates a character string in hexadecimal format.
ex) When reading the D-Register from Temp. PV(D0001) to Temp. SP(D0002).
- Transmission : [stx]01RSD,02,0001[cr][lf]
- Transmission ( Include Check Sum) : [stx]01RSD,02,0001C5[cr][lf]
([stx] = 0x02, [cr] = 0x0d, [lf] = 0x0a)
When Temp. PV value is 50.0 and Temp. SP value is 30.0.
- Response : [stx]01RSD,OK,01F4,012C[cr][lf]
- Response ( Include Check Sum) : [stx]01RSD,OK,01F4,012C19[cr][lf]
Display procedure of the Temp. PV value.
1 Convert hexadecimal to decimal : 01F4(hexadecimal) 500(decimal)
2 converted value * 0.1 : 500 * 0.1 50.0